Safety and Health at Work
2017 Volume.8 No. 2 p.151 ~ p.155
Safety Evaluation of the Lighting at the Entrance of a Very Long Road Tunnel: A Case Study in Ilam
Mehri Ahmad

Hajizadeh Roohalah
Dehghan Somayeh Farhang
Nassiri Parvin
Jafari Sayed Mohammad
Taheri Fereshteh
Zakerian Seyed Abolfazl
Abstract
Background: At the entrance of a tunnel, reflection of sunlight from the surrounding environment and a lack of adequate lighting usually cause some vision problems. The purpose of this study was to perform a safety evaluation of lighting on a very long road in Ilam, Iran.

Methods: The average luminance was measured using a luminance meter (model S3; Hagner, Solna, Sweden). A camera (model 108, 35-mm single-lens reflex; Yashica, Nagano, Japan) was used to take photographs of the safe stopping distance from the tunnel entrance. Equivalent luminance was determined according to the Holliday polar diagram.

Results: Considering the average luminance at the tunnel entrance (116.7 cd/m2) and using Adrian's equation, the safe level of lighting at the entrance of the tunnel was determined to be 0.7.

Conclusion: A comparison between the results of the safe levels of lighting at the entrance of the tunnel and the De Boer scale showed that the phenomenon of black holes is created at the tunnel entrance. This may lead to a misadaptation of the drivers¡¯ eyes to the change in luminance level at the entrance of the tunnel, thereby increasing the risk of road accidents in this zone.
KEYWORD
black hole, De Boer scale, safe level of lighting, tunnel lighting