Àá½Ã¸¸ ±â´Ù·Á ÁÖ¼¼¿ä. ·ÎµùÁßÀÔ´Ï´Ù.
KMID : 0380619870190060486
Korean Journal of Food Science and Technology
1987 Volume.19 No. 6 p.486 ~ p.491
The Heat Pump Application to the Food Concentration
½Åµ¿È­/Shin, Dong Hwa
±èº´»ï/°­Åë»ï/¹Ú³ëÇö/Kim, Byeong Sam/Kang, Tong Sam/Park, Noh Hyun
Abstract
The performance and applicability to food concentration of heat pump were investigated. During heating the water of spa from 43¡É to 51¡É, COP¢¥s of heat pump (R-12, 150 HP) were 4.03 at heating part and 3.5 at cooling part. And, the efficiency of compressor (¥á) was 0.477. While the city water was heated to 39¡É by heat pump (R-22, 10 HP), its COP¢¥s were 3.0 at heating part and 1.87 at cooling part. During concentrationg sucrose solution by centrifugal evaporator (ALFA-LAVAL CO, CTIB) with heat pump, heat capacity for condensating water vapor was required greater 15% than the latent heat for concentrating and then the overall heat transfer coefficient was 1196 Kcal/§³.h.¡É. When low temperature concentration (30-35¡É, 28-40 Torr) of garlic extract was carried out by the water of 60¡É and 15¡É adjusted by heat pump, the ratio of heat capacity for concentrating vs. that for condensating of water vapor was 0.961.
KEYWORD
FullTexts / Linksout information
Listed journal information
ÇмúÁøÈïÀç´Ü(KCI)