KMID : 0896220020220010215
|
|
Journal of Daegu Health College 2002 Volume.22 No. 1 p.215 ~ p.227
|
|
An Investigation of Pressure Setting for Fire Pump
|
|
Choi Young-Sang
|
|
Abstract
|
|
|
This investigation was performed to show the methode for pressure setting of fire pump. Following methods are recommended. 1. The jokey pump start point should be 0.5¡l.0§¸/§² less than the main pump stop point. 2. The fire pump(main pump) start point should be 0.5§¸/§² less than the jokey pump start point. 3. The fire pump and the jokey pump stop point should equal the rating discharge pressure.
|
|
KEYWORD
|
|
|
|
FullTexts / Linksout information
|
|
|
|