KMID : 0948820180240020037
Korea Institute of Healthcare Architecture Journal
2018 Volume.24 No. 2 p.37 ~ p.44
A Numerical Study on Coughed Particle Dispersion and Deposition in Negative Pressure Isolation Room according to Particle Size
Jung Min-Ji

Hong Jin-Kwan
Abstract
Purpose: This study investigates the influences of coughing direction and healthcare worker¡¯s location on the transport characteristics of coughed particles in airborne infection isolation room (AIIR), which is commonly called negative pressure isolation room, with a downward ventilation system.

Methods: Computational Fluid Dynamics (CFD) was used to simulate the airflow and for tracing the behavior of particles.
Results: The results show that the airflow pattern and coughing direction have a significant influence on the characteristics of particle dispersion and deposition. When healthcare workers are in the isolation room with the patient who is lying on the bed, it is recommended to be located far from the anteroom to reduce the exposures from infectious particles. And when the patient is lying, it is more effective in removing particles than when the patient is in Fowler¡¯s position. Although it is an isolation room that produces unidirectional flow, coughing particles can spread to the whole room and a large number of particles can be deposited onto patient, bed, side rails, healthcare worker, ceiling, floor, and sidewall.
Implications: Following the patients¡¯ discharge or transfer, terminal cleaning of the vacated room, furniture, and all clinical equipment is essential. Also, it is necessary to establish detailed standard operating procedure (SOP) in order to reduce the risk of cross-contamination.
KEYWORD
Coughed particle, Airborne Infection, Computational Fluid Dynamics (CFD), Negative Pressure Isolation Room, Particle Dispersion and Deposition